The very latest version of the best selling PAT tester on the market. Revised to comply with the new IET Code of Practice 5th Edition 2020.
Technical Specifications
Earth Continuity | |
---|---|
Test Current | +/- 200mA DC |
Display Range | 0.00 – 19.99Ω |
Pass Value | 0.1Ω/0.2Ω/0.3Ω |
IEC Lead Test | |
---|---|
Tests Performed | Earth continuity, Insulation resistance, Live, neutral continuity and polarity |
Equivalent Leakage Class II | |
---|---|
Test Voltage | 40V, 50Hz AC nominal |
Display Range | 0.10 – 19.99mA |
Pass Value | 5mA |
Insulation Range | |
---|---|
Test Voltages | 250V/500VDC |
Display Range | 0.20 – 19.99MΩ |
Pass Value | 1MΩ/2MΩ |
Equivalent Leakage Class I | |
---|---|
Test Voltage | 40V, 50Hz AC nominal |
Display Range | 0.10 – 19.99mA |
Pass Value | 5mA |
Power Socket Test | |
---|---|
Input Voltage Range | 230V +10% – 15% AC |
Indicators | Line to earth voltage, Line to neutral voltage, Neutral earth |
Weight and Dimensions | 800g/11cm (w) x 5.5cm (d) 27cm (l) |
Power Source
Power Source | 6 x AA type disposable batteries |